Electrical · Protection & Switchgear

MCCB Size Calculator

Calculate Smarter. Work Faster.

Required MCCB trip rating and minimum fault breaking capacity, from full load current and available fault current at the installation point.

MCCB Size Details

Enter load power and voltage for DC, single-phase or three-phase supply — or switch to a known full load current. Then add the available fault current at the installation point.

Input Method
Supply Type

Don’t know it? Work it out with the Short Circuit Current Calculator.

I = P ÷ (√3 × V × PF) MCCB ≥ FLC × duty factor Breaking capacity ≥ Isc
Preliminary MCCB Trip Rating

Enter values and hit calculate

Min. Required Icu
Typical Frame Class
Scope of this result

This is a preliminary current-rating estimate from a configurable duty factor. Final selection must be verified against the applicable code, cable ampacity, load type, trip characteristics, coordination with adjacent devices, and the manufacturer's data.

Icu must be at least the available fault current at the operating voltage; check Ics separately where the circuit has to return to service after a fault. Frame class is manufacturer-dependent — treat it as an indication, not a specification.

Motor circuits and transformer feeders are sized on different bases (starting inrush, inrush current and coordination) and are not covered by this preliminary calculation.

Breakdown

Enter values above to see a breakdown.

Did this solve your problem?

Created by Umasankar Maity — B.Tech in Electrical Engineering, with 11+ years of industrial maintenance experience.

Reviewed by the ElectroMechCalc editorial team.

Last reviewed: September 2026  |  Calculation method: preliminary trip rating = full load current × design allowance × a configurable continuous-duty factor (1.25 by default), rounded up to the next available rating, with required Icu checked separately against the prospective fault current

How it works

How MCCB Rating and Breaking Capacity Are Determined

An MCCB (Molded Case Circuit Breaker) protects higher-current circuits than a typical MCB, and its selection needs two independent checks to be complete: the trip rating (does it carry normal load current with proper margin, and trip appropriately on overload) and breaking capacity (can it safely interrupt the maximum fault current available at its location). Both checks matter, and neither one alone is sufficient.

Check 1 — trip rating. The rating must carry full load current with continuous-duty margin, then round up to the next standard size:

Trip rating
IMCCB IFLC×1.25

Round the result up to the next standard MCCB trip rating. The 1.25 factor is the continuous-duty margin; confirm the value required by the code in force locally.

Check 2 — breaking capacity. Independently, the device must be able to interrupt the fault current available where it is fitted:

Breaking capacity
Icu Isc

Isc is the prospective fault current at that point, set by the supply transformer and the impedance upstream. Round up to the next breaking capacity offered for that frame and trip rating.

Worked example: a distribution circuit has a full load current of 250 A, and the available fault current at its panel location is 25 kA (perhaps calculated using the Short Circuit Current Calculator for the upstream transformer). Trip rating = 250 × 1.25 = 312.5 A, rounded up to the next common rating, 315 A. That is the trip rating, not the frame — a 315 A trip unit is typically supplied in a 400 A frame class, but which frame carries which trip rating is a manufacturer decision, so confirm it against the catalogue. Separately, the available fault current of 25 kA sets the minimum required Icu, so a device rated 25 kA or higher at the operating voltage is needed.

Why both checks are independent, and why both have to pass: trip rating and breaking capacity address entirely different failure modes. An MCCB with adequate trip rating but inadequate breaking capacity might handle normal load and even overload conditions perfectly well, right up until a genuine short circuit occurs that it can't safely interrupt — a rare but potentially catastrophic failure mode. Conversely, an MCCB with excellent breaking capacity but an undersized trip rating would nuisance-trip under normal load, an operational nuisance but not a safety hazard. Both checks need to pass for a genuinely correct MCCB selection.

Frame size and its relationship to trip rating: a given MCCB frame size (the physical case dimensions and mechanism) typically supports a range of trip ratings, often via interchangeable or field-adjustable trip units, up to that frame's maximum current. Selecting a frame size larger than strictly necessary for the trip rating alone can sometimes be justified for other reasons (allowing a higher breaking capacity option, planning for a future trip rating increase without a frame replacement, or standardizing on fewer distinct frame sizes across a facility for spares simplification) — but shouldn't be the default choice without a specific reason, since larger frames typically cost more and take more panel space.

Understanding Icu vs Ics in practical terms: Icu (ultimate breaking capacity) confirms the breaker can safely interrupt a fault at that current level at least once, without necessarily remaining serviceable afterward — think of it as "survives the event, may need replacement or service after." Ics (service breaking capacity, expressed as a percentage of Icu, commonly 50%, 75%, or 100% depending on the specific breaker) confirms the breaker remains fully functional and can be immediately returned to service after interrupting a fault at that level. For a circuit that absolutely must return to service quickly after any fault (a critical process, life-safety system), checking Ics against expected fault current, not just Icu, gives a genuinely more conservative and appropriate design margin.

Coordination between MCCBs at different distribution levels: a facility's main incoming MCCB, sub-distribution MCCBs, and final circuit MCCBs (or MCBs) form a hierarchy where each level should ideally trip only for faults within its own downstream zone, not for faults in a more distant zone that a closer, smaller device should have already cleared. Achieving this selective coordination across multiple levels, especially where adjustable-trip MCCBs are involved, is a more detailed exercise than basic sizing alone, often requiring the manufacturer's specific time-current curve data and, for larger or more critical systems, dedicated coordination study software.

Summary: take a preliminary trip rating as FLC × the duty factor your code or the manufacturer specifies (1.25 by default here) rounded up to the next available rating, and separately confirm that the minimum required Icu ≥ the available fault current at the installation point, at the operating voltage, checking Ics rather than only Icu where continued service after a fault matters. Re-verify breaking capacity whenever upstream system changes could increase available fault current, and always check protection coordination with adjacent devices before finalizing selection.

Why MCCBs, specifically, warrant this more rigorous two-check process: MCCBs are typically deployed at higher current levels and closer to the higher-fault-current parts of a distribution system (main switchboards, large sub-distribution boards) than smaller MCBs further downstream, where available fault current has already been reduced by intervening cable and busbar impedance. This is exactly why breaking capacity verification is treated as a standard, expected part of MCCB selection in a way that's sometimes glossed over for smaller, further-downstream MCBs where fault current has already dropped to a level most standard MCB breaking capacities comfortably handle — though the same principle technically applies at every level, it becomes practically more critical closer to the source.

Working with manufacturer selection tools: most major MCCB manufacturers provide selection software or detailed catalogs that let you input trip rating and fault current requirements directly, returning specific compatible product options with their exact frame size, trip unit type, and breaking capacity combinations — this calculator's role is to help you understand and independently verify the underlying sizing logic before or alongside using such manufacturer-specific tools, not to replace the manufacturer's own detailed, product-specific selection process for a final purchase decision.

Worked Example

FLC=250 A, available fault current 25 kA: trip rating = 250 × 1.25 = 312.5 A → 315 A trip rating, typically in a 400 A frame class (manufacturer-dependent). Minimum required Icu = 25 kA at the operating voltage.

MCCB selection involves several factors beyond current rating and breaking capacity alone — including frame size, adjustable trip unit settings, utilization category (some MCCBs are rated Icu for maximum breaking capacity and Ics for service breaking capacity, which can differ), and specific protection coordination requirements. Always verify final MCCB selection against the manufacturer's technical data, the applicable electrical code, and have the design reviewed by a qualified electrical engineer.

Formulas

Finding Full Load Current Before You Size the MCCB

The calculator above starts from full load current. Where only the load rating is known, current comes first — and the form of the equation depends on whether the voltage you have is line-to-line or line-to-neutral.

Three-phase, line-to-line voltage
I= P √3 × VLL × PF

P in watts, VLL the line-to-line voltage, PF the load power factor. √3 is commonly taken as 1.732.

Three-phase, line-to-neutral voltage
I= P 3 × VLN × PF

Same current, different voltage reference. Since VLN = VLL ÷ √3, the √3 becomes a 3 — using √3 with a line-to-neutral voltage understates the current by a factor of √3.

Single-phase
I= P V × PF

No √3 term. For a resistive load such as heating, PF is 1 and drops out entirely.

Where a design allowance for future load growth is carried, it multiplies the computed current before the MCCB margin is applied:

With a design allowance
Id= P √3 × VLL × PF × ( 1+ m 100 )

m is the allowance as a percentage. This is a planning figure chosen by the designer, not a code requirement — and it is separate from the 1.25 continuous-duty factor applied afterwards.

Worked example

A 75 kW three-phase load at 415 V line-to-line and 0.85 power factor, with no design allowance:

Step 1 — full load current
I= 75,000 1.732 × 415 × 0.85 =122.8 A

Checking the same load against line-to-neutral voltage: VLN = 415 ÷ √3 = 239.6 V, and 75,000 ÷ (3 × 239.6 × 0.85) = 122.8 A — the two forms agree, as they must.

Step 2 — trip rating
IMCCB 122.8×1.25 =153.5 A

Rounded up to the next standard step, a 160 A trip rating — typically on a 250 A frame. Breaking capacity is then checked separately against the fault current at that board.

Two cautions on using a computed current. It is only as good as the efficiency and power factor assumed, so where a motor or machine nameplate exists, the nameplate current is the figure to use. And for motor circuits the short-circuit device is sized on a different basis again, because starting inrush has to pass without tripping.

What the three sizing inputs mean

Two of the calculator's inputs shape the trip rating and one shapes the breaking capacity. They are independent of each other, and mixing them up is the usual reason two engineers get different answers from the same circuit.

Input What It Is Affects
Design allowance (%) An optional planning margin for load you expect to add later, applied to the calculated current before anything else. It is a design decision, not a code requirement, and 0% is a perfectly normal entry when sizing for the present load. Trip rating
Continuous-duty factor The multiplier that gives headroom above steady operating current on a circuit loaded continuously. 1.25 reflects the widely used 125% basis for continuous loads; some codes and devices call for a different figure, which is why it is editable rather than fixed. It does not cover motor starting inrush — that is a separate sizing basis. Trip rating
Available fault current (kA) The prospective short-circuit current the supply can push into a fault at that point, set by the transformer rating and impedance less the impedance of everything upstream of the board. Nothing about the load changes it. Breaking capacity

Applied in order: current × (1 + allowance) × duty factor, rounded up to the next standard rating — then the breaking capacity checked separately against the fault current. A breaker can pass one check and fail the other, and both have to pass.

Definition

What Is an MCCB? Full Form and Meaning

MCCB stands for Moulded Case Circuit Breaker — spelled Molded Case Circuit Breaker in US usage, the same device either way. The name describes its construction: the operating mechanism and contacts are sealed inside a moulded insulating case rather than assembled in an open frame.

It is a protective device for higher-current circuits, carrying normal load current and disconnecting automatically on overload or short circuit. Two ratings define it: a trip rating in amperes (the current it is set to protect) and a breaking capacity in kiloamperes (the fault current it can safely interrupt). Typical trip ratings run from about 16 A to 1600 A and beyond, with breaking capacities from roughly 10 kA to 100 kA depending on frame and model.

MCCBs sit between miniature breakers on final circuits and air circuit breakers on large switchboard incomers, and are the usual choice for distribution boards, sub-mains, large motor feeders and machine supplies.

Abbreviation Full Form What It Protects Against
MCBMiniature Circuit BreakerOverload and short circuit on final circuits, fixed rating, typically up to about 125 A
MCCBMoulded Case Circuit BreakerOverload and short circuit at higher currents, adjustable trip, typically 16–1600 A and above
MPCBMotor Protection Circuit BreakerMotor overload and short circuit, with a trip characteristic built around starting inrush
RCCBResidual Current Circuit BreakerEarth leakage only — it provides no overload or short-circuit protection
RCBOResidual Current Breaker with OvercurrentEarth leakage plus overload and short circuit in one device
ELCBEarth Leakage Circuit BreakerEarth faults; the older voltage-operated type is largely superseded by the current-operated RCCB
ACBAir Circuit BreakerOverload and short circuit on large incomers, typically from around 630 A upward

The short version: an MCB and an MCCB do the same job at different scales, an MPCB does it with a motor-shaped trip curve, and an RCCB or ELCB does an entirely different job — detecting current leaking to earth, not excess current in the circuit. That is why an RCCB is never a substitute for an MCCB; the two are routinely installed together. A side-by-side comparison of all five devices, with trip curves and selection guidance, is covered in detail on the MCB vs MCCB vs RCCB vs ELCB vs MPCB guide.

kA Rating

How to Calculate the Breaking Capacity of an MCCB

Breaking capacity is not chosen from the load — it comes from the fault current the supply can deliver at that point. The usual starting figure is the fault level at the transformer secondary, which depends on the transformer rating and its percentage impedance.

Step 1 — transformer full load current
IFL= S √3 × VLL

S is the transformer rating in VA (a 1000 kVA unit is 1,000,000 VA) and VLL the secondary line-to-line voltage.

Step 2 — prospective fault current
Isc= IFL× 100 %Z

%Z is the transformer's percentage impedance from its nameplate — commonly 4% to 6% on distribution units. A lower %Z means a stiffer supply and a higher fault current.

Worked example

A 1000 kVA transformer, 415 V secondary, 5% impedance:

Result
Isc= 1,000,000 1.732 × 415 × 100 5 =27.8 kA

Transformer full load current is 1391 A; at 5% impedance the fault level is about 27.8 kA. The MCCB at that board therefore needs a rated breaking capacity of at least 27.8 kA — in practice the next standard step, 36 kA.

Three qualifications matter before treating that number as final.

It is the value at the transformer terminals. Fault current falls as you move downstream, because cable and busbar impedance adds up. A board fed by a long run may see considerably less, which is why a full calculation accounts for the impedance of each section rather than applying the transformer figure everywhere.

Running motors add to it. Induction motors feed current back into a fault for the first few cycles, typically several times their own full load current. On a motor-heavy installation that contribution is part of the fault level the breaker must interrupt.

Check the rating at your operating voltage. Breaking capacity is declared at a stated voltage and falls as voltage rises, so a figure quoted at 415 V does not carry over to a 480 V or 690 V system. Where continued service after a fault matters, compare the fault level against Ics rather than only Icu.

Don’t have the fault current figure?

The Short Circuit Current Calculator takes the transformer rating in kVA, the line-to-line secondary voltage and the nameplate %Z and returns the prospective fault current directly — the same two steps worked through above. Take that result back to the fault current field in this calculator to get the minimum required Icu.

Settings

MCCB Trip Unit Settings and What Each One Does

Sizing picks the device; the trip unit decides how it behaves. A thermal-magnetic MCCB usually offers one adjustment — the thermal setting, typically 0.7 to 1.0 times the breaker's nominal rating, with the magnetic element fixed or switchable in coarse steps. An electronic trip unit exposes several, labelled to the same convention across most manufacturers.

Setting Function Typical Adjustment
InNominal rating of the trip unit or sensor — the base every other setting refers toFixed by the unit fitted
Ir (L)Long-time pickup: the overload threshold, set to the circuit's design currentAbout 0.4 to 1.0 × In
trLong-time delay: how long an overload is tolerated before trippingSeconds to minutes at a stated multiple of Ir
Isd (S)Short-time pickup: responds to heavy fault current with a deliberate delay, so a downstream device can clear firstAbout 1.5 to 10 × Ir
tsdShort-time delay: the interval that makes selectivity with downstream devices possibleTypically 0 to 0.5 s
Ii (I)Instantaneous pickup: trips with no intentional delay on a severe faultAbout 2 to 15 × In, sometimes defeatable
Ig (G)Earth-fault pickup, where the unit includes ground-fault protectionAbout 0.2 to 1.0 × In with its own delay

The setting that follows directly from this calculator is Ir: choose the breaker from the standard rating, then dial the long-time pickup down to the circuit's actual design current rather than leaving it at the frame maximum. A 250 A breaker protecting a 160 A circuit left at full setting gives that circuit no meaningful overload protection at all.

The short-time and instantaneous settings are where coordination lives. Getting them right across several levels of distribution needs the manufacturer's time-current curves and, on larger systems, a dedicated coordination study — it is not something a single-device calculation can settle. Ranges above are indicative; the actual adjustment steps come from the specific trip unit's documentation.

Rating Chart

MCCB Rating Chart: Standard Sizes, Frames and Breaking Capacities

MCCB trip ratings follow a widely used preferred series rather than a single universal standard — the exact steps offered differ by manufacturer and product line. A calculated value is rounded up to the next rating actually available. These are the steps this calculator selects from:

Band Standard Trip Ratings (A)
Small16, 25, 32, 40, 50, 63
Medium100, 125, 160, 200, 225, 250
Large315, 400, 500, 630
Very large800, 1000, 1250, 1600

Frame size is a separate axis. One frame covers a band of trip ratings and offers a choice of breaking capacities, so the same 250 A rating can be ordered at 25 kA or at 65 kA depending on the fault level it faces:

Frame Class Trip Range Typical Icu Options
100 A class16–100 A16, 25, 36, 50 kA
250 A class125–250 A25, 36, 50, 65 kA
400 A class250–400 A36, 50, 65, 85 kA
630 A class400–630 A36, 50, 65, 85 kA
800–1600 A class630–1600 A50, 65, 85, 100 kA

Trip rating and frame class are two different numbers. A 315 A trip unit is commonly supplied in a 400 A frame class, so a calculated 315 A rating does not mean a 315 A frame — which frame carries which trip rating is a manufacturer decision. These are illustrative ranges; exact frame classes, trip ranges and available Icu options vary by manufacturer and product line, so always confirm against the actual catalogue for final selection. Note that higher breaking capacity options are typically available within the same frame size at a cost premium.

Trip range overlap between adjacent frame sizes (visible in the table above, where the 250A frame's range partially overlaps the top of the 100A frame's practical ceiling) means the same trip rating can sometimes be achieved with more than one frame size — in these overlap zones, the choice often comes down to whether the higher breaking capacity options available in the larger frame are actually needed, or whether the smaller, less expensive frame's breaking capacity options are already sufficient for the actual available fault current at that location.

Common Mistakes

Common Mistakes When Sizing an MCCB

1. Sizing an MCCB by trip rating alone, without checking breaking capacity. This is the single most serious MCCB sizing mistake — an adequately rated but breaking-capacity-inadequate MCCB is a genuine safety hazard, not just a performance shortfall, since it may fail during a genuine fault rather than safely clearing it.

2. Using Icu (ultimate breaking capacity) where Ics (service breaking capacity) is the more appropriate check. For circuits where continued operation after clearing a fault matters, Ics (typically lower than Icu) is the more conservative and often more appropriate figure to compare against available fault current, not the higher Icu rating alone.

3. Not re-verifying breaking capacity after a system upgrade. A transformer upgrade, added generator, or other change that increases available fault current at an MCCB's location can push actual fault current above a previously adequate breaking capacity rating — any such system change should trigger re-verification of downstream MCCB breaking capacities.

4. Selecting an oversized frame "to be safe" without checking economics. While adequate breaking capacity is mandatory, jumping to an unnecessarily large frame size when a smaller frame with an appropriate breaking capacity option would suffice adds unnecessary cost \u2014 match frame size to actual requirements, not just the largest available option.

5. Ignoring protection coordination with upstream and downstream devices. An MCCB correctly sized in isolation can still create a coordination problem if it doesn't reliably clear a fault before an upstream device operates unnecessarily — check time-current coordination across the full distribution hierarchy, not just each device's individual rating and breaking capacity.

6. Assuming a single MCCB adequately protects a motor without additional consideration. Motor circuits typically need instantaneous trip settings that tolerate starting current alongside separate, more sensitive overload protection \u2014 a standard MCCB sized only by the general continuous-duty formula, without motor-specific trip curve consideration, may not provide appropriate motor protection.

7. Selecting frame size without considering trip range overlap between adjacent frames. The same trip rating can sometimes be achieved in more than one frame size — not checking whether a smaller, less expensive frame's breaking capacity options are already sufficient can lead to an unnecessarily larger, costlier frame selection.

8. Relying entirely on this calculator's simplified sizing instead of manufacturer-specific selection tools for final purchase. This calculator helps verify the underlying sizing logic, but final MCCB selection should reference the specific manufacturer's actual product catalog and technical data for exact available combinations of frame, trip rating, and breaking capacity.

FAQ

Frequently Asked Questions

What is the formula for MCCB trip rating? +

This calculator takes a preliminary trip rating as full load current × an optional design allowance × a continuous-duty factor that you set, defaulting to 1.25 (a 25% allowance), rounded up to the next available rating. That default reflects the widely used 125% basis for continuously loaded circuits, but it is not a universal rule: the final rating depends on the code in force locally, the load type, cable ampacity, ambient and installation conditions, coordination with adjacent devices, and the manufacturer’s data. Motor circuits and transformer feeders are sized on different bases again.

Why does MCCB selection also require checking breaking capacity, not just current rating? +

An MCCB must be able to safely interrupt the maximum fault current that could occur at its installation point without failing catastrophically — its breaking capacity (rated in kA) must be at or above the available fault current at that specific point in the system. A correctly current-rated MCCB with inadequate breaking capacity is a serious safety hazard, since it may not be able to safely clear a genuine short circuit.

What is the difference between Icu and Ics ratings on an MCCB? +

Icu (ultimate breaking capacity) is the maximum fault current the breaker can interrupt once, verified by a test sequence that doesn't require the breaker to remain fully serviceable afterward. Ics (service breaking capacity) is typically a lower value, representing the fault current the breaker can interrupt while remaining fully functional for continued normal service afterward — for critical circuits where continued operation after a fault matters, checking Ics (not just Icu) against expected fault current is the more conservative and often more appropriate check.

What does MCCB frame size mean, and why does it matter beyond the trip rating? +

Frame size describes the physical case size and the maximum current rating that frame can be built to support — a single frame size typically accommodates a range of trip ratings (via interchangeable or adjustable trip units) up to its maximum. Frame size affects breaking capacity options, physical dimensions, and sometimes cost, so selecting an appropriately sized frame (not the largest available "to be safe") is part of a complete, economical MCCB specification.

Should I use an adjustable or fixed trip MCCB? +

Adjustable (electronic) trip MCCBs allow fine-tuning the overload and short-circuit trip settings within a range, useful for precise protection coordination or when load current may change over time — fixed thermal-magnetic trip MCCBs are simpler and often more economical for straightforward applications where the exact trip point doesn't need fine adjustment. The choice depends on the specific application's need for precision and flexibility versus simplicity and cost.

How does MCCB sizing relate to upstream and downstream protection coordination? +

Similar to fuse and MCB coordination, an MCCB's time-current characteristic (and, for adjustable trip units, its specific settings) needs to coordinate with other protective devices in the system, so that a fault trips only the closest upstream device rather than cascading to trip a larger, further-upstream device unnecessarily — this coordination check is a separate exercise from basic current rating and breaking capacity sizing, important for larger or more complex distribution systems.

Can an MCCB be used for motor protection like an MCB or fuse? +

Yes, though motor circuits often use MCCBs with specific motor-protective trip characteristics or combine an MCCB with a separate motor overload relay, similar to fuse and MCB motor protection practice — the same principle applies: instantaneous/magnetic trip settings need to tolerate normal motor starting current, while a more sensitive separate or integrated overload element handles genuine running overload protection.

What happens if an MCCB's breaking capacity is exceeded during a real fault? +

An MCCB asked to interrupt a fault current beyond its rated breaking capacity can fail to safely clear the fault, potentially with catastrophic results including explosion, fire, or a fault that persists uncontrolled — this is a serious safety failure mode, which is why breaking capacity verification against actual available fault current is a mandatory, not optional, part of MCCB selection.

Do I need to recheck MCCB breaking capacity if the electrical system is later modified? +

Yes — any change that could increase available fault current at an MCCB's location (a larger or lower-impedance transformer upgrade, a new generator or additional fault-current-contributing source added to the system) should trigger a re-verification of every downstream MCCB's breaking capacity against the new, potentially higher, available fault current, since a previously adequate breaking capacity rating can become inadequate after such a system change.

Why does the same load give a different formula for line-to-line and line-to-neutral voltage? +

It does not give a different current, only a different equation for the same current. Line-to-neutral voltage is line-to-line divided by √3, so substituting it turns the √3 in the denominator into a 3. A 75 kW load at 0.85 power factor draws 122.8 A whether the arithmetic uses 415 V with √3 or 239.6 V with 3. Using √3 together with a line-to-neutral voltage understates the current by a factor of √3, which is a common source of undersized protection.

What is the full form of MCCB? +

MCCB stands for Moulded Case Circuit Breaker, written as Molded Case Circuit Breaker in US usage. The name comes from its construction: the contacts and operating mechanism are sealed inside a moulded insulating case. It protects a circuit against both overload and short circuit, and is defined by a trip rating in amperes and a breaking capacity in kiloamperes.

How do you calculate the kA breaking capacity needed for an MCCB? +

Work out the prospective fault current at the installation point. From a transformer, take its full load current, IFL = S ÷ (√3 × VLL), then divide by the percentage impedance expressed as a fraction: Isc = IFL × 100 ÷ %Z. For a 1000 kVA, 415 V, 5% impedance transformer that gives about 27.8 kA, so the breaker needs at least that rating — in practice the next standard step, 36 kA. Fault current falls downstream as cable impedance adds up, and running motors contribute to it for the first few cycles.

What are the standard MCCB sizes? +

Trip ratings follow a preferred series — commonly 16, 25, 32, 40, 50, 63, 100, 125, 160, 200, 225, 250, 315, 400, 500, 630, 800, 1000, 1250 and 1600 A. A calculated rating is rounded up to the next value available, and the exact steps offered vary by manufacturer and frame.

What does the Ir setting on an MCCB do? +

Ir is the long-time pickup, the overload threshold, and it should be set to the circuit's actual design current rather than left at the breaker's maximum. A 250 A breaker protecting a 160 A circuit at full setting gives that circuit no meaningful overload protection. Electronic trip units add Isd and tsd for short-time response, Ii for instantaneous, and often Ig for earth fault.

Explore More Categories