Electrical · Protection & Switchgear

MCB Size Calculator

Calculate Smarter. Work Faster.

Free MCB size calculator — enter full load current and load type to instantly get the correct MCB rating and trip curve type (B, C, or D).

MCB Size Details

Enter the load current, pick a trip curve and a pole configuration — the calculator returns the rating, the actual instantaneous trip band in amps, and which conductors the breaker disconnects.

MCB = FLC × 1.25
Required MCB Rating

Enter values and hit calculate

Curve Type
Instantaneous Trip Band
Poles
Conductors Switched
Breakdown

Enter values above to see a breakdown.

Did this solve your problem?

Created by Umasankar Maity — B.Tech in Electrical Engineering, with 11+ years of industrial maintenance experience.

Reviewed by the ElectroMechCalc editorial team.

Last reviewed: September 2026  |  Calculation method: rating = full load current × 1.25 rounded up to the next available rating; instantaneous trip band = rating × the curve multiplier, with B/C/D per IEC 60898-1 and K/Z per IEC 60947-2

How it works

How MCB Size and Curve Type Are Selected

Rule of thumb: MCB Rating = Full Load Current × 1.25, rounded up to the nearest standard size — a 12 A load needs a 16 A MCB.

Formula: MCB Rating = Full Load Current × 1.25, rounded up to the next rating available. The 1.25 gives headroom above the steady load so the thermal element is not sitting at its limit in normal service. Where the local wiring rules set a different factor for the circuit type, use theirs.

Two elements, one device. The thermal element handles sustained overload and takes seconds to minutes; the magnetic element handles short circuits and operates in milliseconds. The rating sets the thermal behaviour, the curve sets the current at which the magnetic element takes over. That is why a 16 A Type B and a 16 A Type C carry the same load identically but behave completely differently the moment a motor starts.

Standard ratings. The result is rounded up to the preferred series — 6, 10, 16, 20, 25, 32, 40, 50, 63 A and above — so a calculated 15 A becomes a 16 A device, and the cable must be rated for that 16 A, not for the 15 A that was calculated.

Worked example: a small motor circuit drawing 12 A. Rating = 12 × 1.25 = 15 A → 16 A. On a Type C curve that gives an instantaneous band of 80–160 A, which rides through the starting surge but still clears a short circuit in milliseconds.

Summary: rating from the load current, curve from the inrush, poles from the isolation the circuit needs — three independent choices. Whatever the three produce, the rating must not exceed the current-carrying capacity of the cable it protects.

Worked Example

Small motor, FLC=12A, moderate inrush: MCB Rating = 12 × 1.25 = 15A → 16A standard size, Type C curve (trips at 80-160A instantaneous).

MCB rating and curve type selection here uses standard general guidelines — for a final design, confirm the exact starting/inrush characteristics of your specific load against the MCB manufacturer's published curve data, and verify the selected MCB's rating and curve type against the applicable electrical code and any downstream protection coordination requirements. Combine with a residual current device (RCD/RCCB) or use a combined RCBO where earth leakage protection is also required, and have the final panel design reviewed by a qualified electrical engineer.

Reference Table

MCB Trip Curve Types and Their Applications

Curve Instantaneous Band Defined In Typical Application
Type Z2–3×IEC 60947-2Semiconductor and measuring circuits, sensitive electronic equipment
Type A2–3×Manufacturer rangeSemiconductor protection. Not part of the IEC 60898-1 household set and not widely stocked — check availability before specifying
Type B3–5×IEC 60898-1Lighting, heating and other resistive loads; most domestic final circuits
Type C5–10×IEC 60898-1Mixed commercial loads, small motors, air conditioning, fluorescent and LED banks
Type K8–12×IEC 60947-2Industrial motor and transformer circuits where a tighter band than Type D is wanted
Type D10–20×IEC 60898-1Transformers, large motors, welding sets and other heavy-inrush equipment
MCB instantaneous trip bands compared Horizontal logarithmic scale of current as a multiple of rated current, showing the instantaneous trip band of each curve type: Z and A from two to three times, B from three to five, C from five to ten, K from eight to twelve, and D from ten to twenty. The bands of C, K and D overlap. 1x 2x 3x 5x 8x 10x 20x Current as a multiple of rated current (log scale) Z / A 2–3x B 3–5x C 5–10x K 8–12x D 10–20x Below its band a breaker still trips, but on the slower thermal element — seconds to minutes, not milliseconds.
Bands are the standard multiples of rated current, not a time–current curve. Overlap is normal: at 11× rating a Type C, K and D can all be in their instantaneous region.

The band is the only thing separating one curve from another at the same rating. Thermal characteristic, current-carrying capacity and the physical device are identical.

Two points are worth separating, because they are routinely blurred together in curve-type lists. B, C and D are defined in IEC 60898-1, the standard for household and similar circuit breakers — these are the three you will find in any wholesaler. K and Z belong to industrial breakers built to IEC 60947-2, and A appears only in some manufacturers’ semiconductor-protection ranges. Listing all six as if they were interchangeable options on a shelf leads people to specify a curve their supplier does not carry.

The second point is that the bands overlap. A fault at eleven times rated current sits inside the instantaneous region of Type C, Type K and Type D simultaneously — what separates them is behaviour at the lower end, where a Type B has already tripped instantly and a Type D is still waiting on its thermal element. Choosing a curve is choosing how much brief inrush to ignore, not choosing how fast the breaker is.

That has a safety consequence worth stating plainly: a higher curve raises the current needed for an instantaneous trip, so on a long circuit with high loop impedance a Type D may not reach its magnetic threshold during an earth fault at all, and disconnection then falls to the much slower thermal element. Where a curve is raised to stop nuisance tripping, the earth fault loop impedance should be re-checked against the disconnection time the local wiring rules require.

Pole Configuration

MCB Poles: SP, SP+N, DP, TP, TPN and 4P

The pole count answers a different question from the rating and the curve. Rating asks how much current the breaker carries, curve asks how much inrush it tolerates — poles ask which conductors actually get disconnected when it opens. A 16 A Type C behaves identically as a single-pole or a four-pole device; only the isolation changes.

Configuration Conductors Switched Where It Is Used
SP (1P)Line onlyDomestic final circuits — lighting, socket circuits, fans
SP+N (1P+N)Line + neutralSame duty as SP where the neutral must also be isolated, in one module width
DP (2P)Line + neutralHeavier single-phase appliances, water heaters, and wherever supply polarity is not guaranteed
TP (3P)Three phasesThree-phase loads with no neutral — most three-phase motors
TPN (3P+N)Three phases; neutral on a solid link, not switchedThree-phase distribution boards feeding single-phase circuits from a common neutral
4PThree phases + neutralWhere the neutral itself must be broken — generator changeover, some TT arrangements

TPN and 4P are not the same thing

This is the distinction most pole-count lists get wrong by lumping them together. In a TPN device the neutral passes through a solid link: it is brought into the breaker for convenience of wiring, but it is not disconnected when the breaker trips or is switched off. A 4P device has a genuine fourth switched pole. If your reason for wanting the neutral in the breaker is isolation — working safely on the circuit, or separating a generator neutral — a TPN will not do it.

Where a neutral is switched, the order matters: it must not be disconnected before the line conductors, or re-connected after them. Devices designed for the job handle this internally; improvising one by wiring a neutral through a spare pole of an ordinary breaker does not.

Common Mistakes

Common Mistakes When Sizing an MCB

1. Using Type B on a motor circuit. The 3–5× band is exceeded by ordinary starting inrush, so the breaker trips every time the motor starts.

2. Defaulting to Type D everywhere “to be safe”. It is the opposite of safe: a higher curve needs more fault current to trip instantly, which can leave a long circuit relying on the slow thermal element.

3. Treating the MCB as motor overload protection. A breaker sized to pass starting current cannot also catch a modest sustained overload. That needs a separate overload device.

4. Rounding the calculated rating down. Round up to the next available rating, then size the cable for that rating rather than for the calculated figure.

5. Exceeding the cable’s current-carrying capacity. The MCB protects the cable; a rating above the cable’s ampacity protects nothing.

6. Checking the current rating but not the breaking capacity. A correct rating says nothing about whether the device can safely interrupt the fault current available at that board.

7. Not separating thermal from magnetic nuisance tripping. A trip after minutes of running points at the rating or the load; a trip at the instant of switching points at the curve or a genuine fault. They have opposite fixes.

FAQ

Frequently Asked Questions

What is the formula for MCB sizing? +

MCB Rating = Full Load Current × 1.25, rounded up to the next rating available. A 12 A load gives 15 A, which becomes a 16 A device. Where the local wiring rules set a different factor for that circuit type, use theirs.

Which curve type should I use for general lighting and resistive loads? +

Type B. Lighting, heating and other resistive loads draw no meaningful inrush, so the tighter 3–5× band gives faster disconnection on a fault without nuisance tripping.

Which curve type should I use for a motor circuit? +

Type C for most small and medium motors, Type D where inrush is heavy or prolonged — large motors, transformers, welding sets. Type K is the industrial alternative between the two. The motor still needs a separate overload device.

Can I use a higher curve type than necessary just to be safe? +

It stops nuisance trips and weakens protection at the same time. A higher curve raises the current needed for an instantaneous trip, so on a long circuit the magnetic element may not operate during an earth fault at all, leaving disconnection to the much slower thermal element. Re-check the earth fault loop impedance against the disconnection time your wiring rules require.

Does MCB rating alone provide motor overload protection? +

No. An MCB sized to let motor starting current through cannot also protect against a modest sustained overload — the two requirements pull in opposite directions. Motor overload protection comes from a separate overload relay or an MPCB with an adjustable thermal element set to the nameplate current.

What is the difference between an MCB and an MCCB? +

Scale and adjustability. MCBs are fixed-rating devices, typically up to about 125 A, with a fixed curve. MCCBs run to far higher ratings with adjustable trip settings and much higher breaking capacities. An MCB suits final circuits; an MCCB suits sub-mains and large feeders.

Should MCB rating exceed the protected cable's ampacity? +

No. The MCB protects the cable, so its rating must be at or below the cable's current-carrying capacity under the actual installation conditions. Rounding the rating up to a standard size means the cable has to be sized for that standard rating, not for the raw calculated figure.

How do I know the actual inrush current of my specific load to pick the right curve type? +

Nameplate data first, then the equipment manufacturer's documentation. Where neither gives a figure, the curve is chosen from the load class — resistive, motor, or transformer — and confirmed in service: a correctly rated MCB that trips only at start-up is telling you the curve is too tight, not that the rating is wrong.

What is the difference between a Type B and a Type C MCB? +

Only the instantaneous band. Type B trips instantly at 3–5× rated current, Type C at 5–10×. The thermal characteristic is identical, so a 16 A of either carries 16 A indefinitely. Type B suits resistive loads; Type C tolerates the brief surge of small motors and LED driver banks.

What is a Type K and a Type Z MCB used for? +

Type K trips at roughly 8–12×, between C and D, for industrial motor and transformer circuits. Type Z trips at 2–3× for semiconductor and measuring circuits. Both come from industrial breakers built to IEC 60947-2 rather than the IEC 60898-1 set that defines B, C and D, so check availability before specifying one.

What is the difference between a TPN and a 4-pole MCB? +

A TPN device has three protected poles and a neutral on a solid link — the neutral is not broken when it opens. A 4-pole device has a genuine fourth switched pole. If the reason for wanting the neutral in the breaker is isolation, a TPN will not provide it.

Does the number of poles change the MCB rating or trip curve? +

No. A 16 A Type C has the same thermal characteristic and the same instantaneous band whether it is single-pole or four-pole. Poles decide only which conductors are disconnected.

Explore More Categories