Electrical · Free · Instant results

DG Size Calculator

Find the right diesel generator (DG set) capacity in kVA, full-load current, and estimated fuel consumption from your connected load, power factor, and voltage.

Generator Load Details

Pick single or three phase, then enter your load, power factor, voltage, and safety margin.

Single Phase
Three Phase
kVA = kW ÷ PF I = (kVA × 1000) / (√3 × V) Fuel = kW × 0.27 L/hr
How it works

Understanding DG Size Calculation

Sizing a diesel generator (DG set) correctly is a balance between reliability and cost: an undersized generator will stall, overheat, or trip under motor-starting surges and peak demand, while an oversized one runs inefficiently at light load, wastes fuel, and costs more upfront. This calculator estimates the right DG set capacity for a given electrical load by converting the real power demand (kW) into the apparent power (kVA) a generator must be rated for, then matching that figure against standard commercially available DG set sizes. It also estimates the full-load current the DG set will supply and the approximate diesel fuel consumption per hour, both useful figures when planning fuel storage and the outgoing cable or breaker from the generator.

The required DG capacity is found from DG Size (kVA) = Load (kW) ÷ PF, since a generator's nameplate is always rated in kVA while the actual connected load is usually expressed in kW; dividing by the power factor accounts for the reactive power the generator must also supply. A safety margin is then added on top of this calculated value, since real installations rarely run at a perfectly steady, ideal load — motor starting surges, future load additions, and day-to-day demand fluctuations all call for some spare capacity.

The resulting current draw is calculated using I = (kVA × 1000) ÷ (√3 × V) for a three-phase supply, or I = (kVA × 1000) ÷ V for single-phase, which determines the cable and breaker sizing on the generator's output. Fuel consumption is approximated using a commonly used diesel-generator rule of thumb of roughly 0.27 litres per hour for every kW of load, though actual consumption varies by engine efficiency and load factor.

Worked example: A facility has a three-phase connected load of 80 kW at a power factor of 0.8, supplied at 415 V, with a 20% safety margin. The base DG capacity is kVA = 80 ÷ 0.8 = 100 kVA. Adding the 20% margin: 100 × 1.20 = 120 kVA, which would typically be rounded up to the nearest standard DG size of 125 kVA. The full-load current at 415 V is I = (120 × 1000) ÷ (1.732 × 415) ≈ 167.0 A, and estimated fuel consumption is roughly 80 × 0.27 ≈ 21.6 L/hr.

This tool is especially useful for facility engineers and contractors selecting a backup or prime power DG set, sizing the generator's output cable and protection, or estimating fuel budget and tank capacity for continuous or standby operation.

kW vs kVA: Why Generators Are Never Rated in kW Alone

Real power (kW) is the power that actually does useful work — turning a motor shaft, lighting a bulb, heating an element. Apparent power (kVA) is the total power the generator's alternator and windings must be capable of delivering, including the reactive component absorbed and released by inductive loads such as motors, transformers, and fluorescent or induction lighting ballasts. The ratio between the two is the power factor: kW = kVA × PF. Because the generator's physical winding size and heat dissipation are governed by current (and therefore by kVA, not kW), manufacturers always publish a kVA nameplate rating. A DG set rated 100 kVA at 0.8 PF can deliver 80 kW of real power — trying to draw 100 kW of real load from it, even momentarily, will overload the alternator regardless of the kVA figure on the nameplate.

Why Motor Starting Loads Need Extra Margin

Induction motors, pumps, compressors, and air-conditioning compressors typically draw 5 to 7 times their full-load current for a fraction of a second at start-up (direct-on-line starting). A generator sized only for the steady-state running load can experience a large, sudden voltage dip or stall entirely when such a motor starts, especially if the starting motor represents a large fraction of the total connected load. This is one of the main reasons the standard 15–25% safety margin exists, and why installations with large single motors — borewell pumps, chillers, or big compressors — often need either a larger safety margin, a soft starter/VFD on the motor, or a generator explicitly sized for the starting kVA rather than just the running kVA.

How to Use This DG Size Calculator

  1. Select the phase type — single phase for smaller domestic or shop loads, three phase for industrial and commercial installations.
  2. Enter the connected load in kW and the expected power factor (typically 0.8 for a mixed motor and lighting load; check your electricity bill or panel meter for a more accurate figure).
  3. Enter the supply voltage (commonly 230 V single-phase or 415 V three-phase in India) and a safety margin percentage — 15–25% covers most general-purpose backup applications.
  4. Click Calculate DG Size to see the recommended standard DG capacity in kVA, the full-load output current, and the estimated diesel consumption per hour.

Common Mistakes When Sizing a Generator

  • Sizing purely on kW without converting to kVA. Buying a "100 kW" generator when the actual requirement is 100 kVA at 0.8 PF (i.e. only 80 kW usable) is a frequent and costly sizing error.
  • Ignoring motor starting surges. A generator that comfortably handles the running load can still stall or trip when a large motor starts, if no allowance is made for inrush current.
  • Skipping the safety margin. Sizing exactly to the calculated load leaves no headroom for future expansion, seasonal peak loads, or day-to-day demand variation.
  • Using an unrealistic power factor. Assuming PF = 1 for a load that is actually 0.75–0.85 (typical for motor-heavy loads) will undersize the generator; use your actual metered power factor where possible.
  • Confusing standby and prime power ratings. A generator rated for occasional standby duty is not necessarily suitable for continuous, daily prime power operation at the same load — check the manufacturer's duty rating.

Typical DG Set Sizes and Common Applications

DG Size (kVA)Typical ApplicationApprox. Full-Load kW (0.8 PF)
5–10Home / small shop backup4–8 kW
15–30Small office / retail outlet12–24 kW
62.5–125Small commercial building / clinic50–100 kW
160–320Mid-size industrial unit128–256 kW
500–1000+Large factory / data centre / hospital400–800 kW+

Figures are indicative only. Always confirm exact standard DG set sizes and duty ratings with the manufacturer's catalogue.

FAQ

Frequently Asked Questions

Content last reviewed: July 2026

Why is DG capacity rated in kVA instead of kW? +

A generator must be able to supply both the real power (kW) that does useful work and the reactive power drawn by inductive loads like motors. kVA represents this total apparent power the generator's windings and alternator must handle, so nameplates are always rated in kVA rather than kW.

How much safety margin should I add? +

A margin of 15–25% is typical for most facilities, covering motor starting surges and future load growth. Installations with large motors starting direct-on-line, or expected expansion, should lean toward the higher end of that range.

How accurate is the fuel consumption estimate? +

The 0.27 L/hr per kW figure is a widely used field rule of thumb for diesel gensets running near full load. Actual consumption depends on engine efficiency, altitude, ambient temperature, and how lightly or heavily loaded the generator runs, so always cross-check against the manufacturer's fuel consumption chart for critical sizing.

Are these calculators accurate enough for professional use? +

Yes — every formula used is the same standard formula taught in electrical engineering coursework and referenced in field handbooks. That said, for safety-critical or code-compliance decisions, always verify results against your local electrical code and have them reviewed by a licensed engineer.

What size DG set do I need for a home or small office? +

For a typical home backup load of 3–5 kW at 0.8 power factor with a 20% margin, a 5–7.5 kVA single-phase DG set is usually sufficient. For a small office or shop with 15–20 kW connected load, a 25–30 kVA three-phase set is a common starting point, though the exact figure depends on motor starting loads such as air conditioners or pumps. Enter your own numbers above for a precise recommendation.

Should I size a DG set for standby or prime power use? +

Standby-rated generators are sized for occasional backup use during grid outages and typically run at a lower average load factor, while prime-rated generators are designed for continuous or regular daily operation at a sustained load with a smaller overload allowance. Prime power applications generally need a larger safety margin and a genset explicitly rated for continuous duty by the manufacturer.